CHAPTER FOUR - OPTIONS: SYSTEM
34
SG-System I Operating Manual
4
Option 013: Buzzer Tone
Default (00)
A tone will sound when the SG-System I, having received an alarm, is unable to forward the alarm message to either the Serial or TCP/IP
automation paths (while in Manual mode). You are able to manipulate this tone via Option 013. The tone generated will continue to pulse
until all unacknowledged events have been acknowledged by the user; this can be done by pressing the Ack button for each event, or the unit
itself transfers from Manual mode to Active mode. If Option 013 is set to ‘0’ or ‘1’, no buzzer tone will sound on receipt of an alarm. Any
other value will produce a tone.
To set the buzzer tone, take the following steps:
1. Navigate to Option 013. Press the Enter button. The current value is displayed on the LCD.
2. Press the Enter button. The value may now be changed.
3. Use the Up and Down buttons to scroll to the desired value.
NOTE: As each tone is selected the SG-system I will sound that tone for a period of 250 msec, allowing the user the oppor-
tunity to judge each tone as it is selected.
4. Having made a selection, press the Enter button.
5. The LCD will prompt you to accept (Y?) or to decline (N?) your changes.
6. Use the Up and Down buttons to select your answer. Press the Enter button.
NOTE: Refer to UL864 Programming Requirements on page 10 if changing the default setting.
Option 014: Receiver Number
Default (01)
The receiver number is used to identify the receiver (or, unit) when communicating to the TCP/IP Automation, the Serial Automation, and
any connected printer. This receiver number applies to all traffic, unless overridden by another option. In the event that such overriding takes
place, it will most likely be a Fallback / Recovery Strategy option.
Option 015: Printer Test
Default (ON)
When this option is enabled, a test signal is sent to all active printers at 0500 hrs and 1700 hrs of every day.
Table 6: Buzzer Tones
IDX Frequency (Hz)
20 1490
25 1990
26 2103
30 2650
33 3149
37 3965
38 4270
39 4530