CHAPTER FIVE - OPTIONS: CHANNELS 1 and 2
71
SG-System I Operating Manual
5
123 3
123 3
333 1
333 1
The SG-System I will interpret this information as 123 31.
The default value of 01 enables Option 198; when set as 00, the option is disabled.
Option 199: Ademco Express
Default (01)
The Ademco 4/1 Express format may cause conflicts with the Sur-Gard DTMF 4/3 checksum format or FBI Super fast without checksum.
You can use this option to inform the line card which of these formats will be used.
00 - Sur-Gard DTMF 4/3 with checksum
01 - Ademco 4/1 Express
02 - FBI without checksum
Option 19A: Error Counter
Default (00)
When you set this option, it will configure the number of consecutive bad pulse rounds before the receiver will automatically hang-up.
The default of 00 means this option is disabled and the receiver must wait for the panel to hang-up first.
Option 19B: Echo Canceller
Default (00)
You can use this option to suppress the incidence of echo on a telephone line. When Option 19B is enabled and an incoming call is anwered,
the receiver will generate a 2100 Hz tone with 180 degrees of phase reversal every 450 msec, for a total length of two seconds.
• 00 - Disabled
• 01 - Enabled
Option 19C: Acron RS-232
Default (01)
You can set this option as 00 to convert the Acron Super Fast format signal into the standard 3/2 or 4/2 format.
1RRLLLssssssAAAAsXssYY[DC4]
Where 1 = protocol number
RR = receiver number
LLL = line number
ssssss = spaces
AAAA = account code
X = Event Code
YY = Zone Number
And to the printer with the library text as
RR-LLL-AAAA-YY-Text
Set this option as 01 to send the Acron Super Fast format to the automation as indicated below: