CHAPTER FIVE - OPTIONS: CHANNELS 1 and 2
72
SG-System I Operating Manual
5
9RRLLLssssAAAACCCCCCCCC[DC4]
Where 9 = protocol number
RR = receiver number
LLL = line number
ssss = spaces
AAAA = account code
CCCC = channel 1-4
CCCC = channel 5-8
[DC4] = terminator
And to the printer with no library text as
RR-LLL-AAAA-CCCCCCCC
Option 19D: Modem II RS-232
Default (01)
In order for the SG-System I to receive the Modem II formats, two of the handshakes should be programmed 0B or 0E. The Modem II RS-
232 option controls how the receiver will output alarms to the automation. This option is a bit selectable option, meaning more than one bit
may be enabled.
Bit 0: OFF select protocol: 1RRLLLssssssAAAAXXYYYY[DC4].
ON select protocol: 6RRLLLssssssAAAAXXYYYY[DC4].
Bit 1: OFF Do not convert to SIA protocol.
ON convert Modem II to SIA protocol: SRRLLL[#AAAA|EYYZZZ][DC4].
Bit 2: OFF Do not convert to SIA with Modem II ASCII text blocks.
ON Convert to SIA protocol with Modem II ASCII text blocks as
SRRLLL[#AAAA|EYYZZZ][DC4] and
RRRLLL[#AAAA|A....][DC4].
Bit 3: OFF Only decode the first 4 digits of Modem II account codes even if more than four are received.
ON Decode up to 10 digits of Modem II account codes.
Use the default value of 0x01 to format the output with 6RRLLL protocol, meaning that it does not convert to SIA, does not process Modem
II text blocks, and only decodes the first 4 digits of Modem II account codes.
NOTE: The lowest bit will also affect the BFSK format decoding.
NOTE: Ensure that the automation software supports settings 02 and 06 if the SIA protocol is desired.
Option 19E: Scantronics Select
Default (00)
You can set this option as 00 to decode 14-Digit DTMF as Scantronics 4-8-1 with Checksum.
You can set this option as 01 to decode 14-Digit DTMF as Scantronics 5-8-1.
Option 19F: Ademco High Speed RS-232
Default (01)
You can set this option as 00 to convert the High Speed format signal into 4-2 format automation:
1RRLLLssssssAAAAsXssYY[DC4]
printer: RR-LLL-AAAA-YY-Alarm