Chapter 3   Ambient Environment and Installation 
3-4 
E. Fuse types 
Drive input fuses are provided to disconnect the drive from power in the event that a component fails in 
the drive’s power circuitry. The drive’s electronic protection circuitry is designed to clear drive output 
short circuits and ground faults without blowing the drive input fuses. Table below shows the N310 
input fuse ratings. 
To protect the inverter most effectively, use fuses with current-limit function. 
Horsepower 
power supply 
standard 
Fuse types 
1/2  15A,     600VAC,    100KA    I.R. 
3 
200-240V 
20A,    600VAC,    100KA    I.R. 
1  5A,     600VAC,    100KA    I.R. 
2  10A,     600VAC,    100KA    I.R. 
3  15A,     600VAC,    100KA    I.R. 
5  20A,     600VAC,    100KA    I.R. 
7.5/10  40A,     600VAC,    100KA    I.R. 
15 
380-480V 
70A,     600VAC,    100KA    I.R. 
※Notice 
z  To avoid shock hazards, do not touch any electrical component when the power is applied or with in 
five minutes after the power is disconnected. Any inspection should be performed after the charge 
indicator goes off. 
z  Do not perform wiring on the inverter with power on. Disregard of this notice may result in serious 
injury.