Chapter 4 Software Index
4-12
04-start/stop command group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
04-00 Starting Method Selection
0:
Normal Start
1: Enable Speed Search
0
04-01 Stopping Method Selection
0: Enhanced braking capacity
1: Coast to stop
2: standard braking capacity
0
04-02 Keypad Stop Button
0: Stop Button Enabled
1:
Stop Button Disabled
0
04-03
Momentary Power Loss and
Restart
0: Momentary Power Loss and Restart disable
1: Momentary power loss and restart enable
2: Momentary power loss and restart enable while
CPU is operating. (According to the capacity of DC
power)
0
04-04
Momentary Power Loss
Ride-Thru Time (Seconds)
0.0 - 2.0 0.5
04-05 Auto Restart Method
0:
Enable Speed Search
1: Normal Start
0
04-06
Auto Restart Delay Time
(Seconds)
0.0 - 800.0 0.0
04-07
Number of Auto Restart
Attempts
0-10 0
04-08 Reset Mode Setting
0: Enable Reset Only when Run Command is Off
1:
Enable Reset when Run Command is On or Off
0
04-09 Direct Running After Power Up
0:
Enable Direct running after power up
1:
Disable Direct running after power up
1
04-10 Delay-ON Timer (Seconds) 1.8 ~300.0 1.8
04-11
Kinetic Energy Back-up
Deceleration Time
0.0:
Disable
0.1~25.0:
KEB Deceleration Time
0.0
04-12
Lower Limit of Power Voltage
Detect
150.0~210.0
/300.0~420.0
190.0
/380.0
04-13
DC Injection Brake Level (%)
@start
0.0~150.0 50.0
04-14
DC Injection Brake Time
(Seconds) @start
0.0~25.5 0.5
04-15
DC Injection Brake Start
Frequency (Hz) @stopped
0.10~10.00 1.50
04-16
DC Injection Brake Level (%)
@Stopped
0.0~150.0 50.0
04-17
DC Injection Brake Time
(Seconds) @stopped
0.0~25.5 0.5

Table of Contents