Step 2 Apply Power to the Drive 
z  Apply AC power to the Drive and observe Operator. Five 7-segment Display 
should read Power Voltage for 2 seconds and then read Frequency/Speed, 
5.00. Five 7-segment Display and FWD LED should be flashed all the time. 
 
Step 3 Check Motor Rotations without Load 
z  Press RUN key (FWD LED should light); five 7-segment Display should run 
from 0.00 to 5.00.   
z  Check motor rotation. 
If it is not correct: 
Press STOP key. Remove AC power. Wait for LED “charge” lamp to extinguish. 
Reverse motor leads T1 and T2.Restart the drive and check new rotation. 
 
Step 4 Check Full Speeds at 50Hz/60Hz 
z  Frequency/Speed can be changed by pressing the up or down Arrow keys. 
To move right or left for next digit, press “<” key.   
Press the READ / ENTER key to set the speed. 
z  Set frequency up to 50Hz/60Hz in accordance with the last rule. 
z  Press RUN key. Check drives acceleration to full speed. 
z  Press STOP key to stop drive and check deceleration. 
 
Step 5 Other Operations 
Run command selection:        00-03(or 00-04) 
Frequency command selection:  00-05(or 00-06) 
For information, see N310 Instruction Manual. 
Please refer to the following pages: 
Set Control Mode (Vector, V/F) .............................…. p. 4-07
 
Set Motor Rated Current .......................................…. p. 4-13 
Set Accel ......................................................................p. 4-08 
Set Decel ..................................................................... p. 4-08 
Set Max Speed ............................................................ p. 4-08 
Set Min Speed ............................................................. p. 4-08