Group5- V/F command group
V/F PATTERN Selection
05-00: Volts/Hz Curve Modification (Torque Boost) (%) =0 ~ 30.0
05-01: Motor no load current(Amps AC) -------------
05-02: Motor rated Slip Compensation (%) = 0.0 ~ 100.0
05-03: v/f Maximum voltage (Vac) 220V series:170.0 ~ 264.0
400V series:323.0 ~528.0
05-04: Maximum Frequency (Hz) = 0.20 ~ 400.0Hz
05-05: Maximum Frequency Voltage Ratio (%) = 0.0 ~ 100.0
05-06: Medium Frequency (Hz) = 0.10 ~ 400.0Hz
05-07: Medium Frequency Voltage Ratio(%) = 0.0 ~ 100.0
05-08: Minimum Frequency (Hz) = 0.10 ~400.0Hz
05-09: Minimum Frequency Voltage Ratio (%) = 0.0 ~ 100.0
05-10: V/F Energy Saving Mode =0: Disabled
=1:Controlled by MFIT at Energy Saving
05-11: V/F Energy Saving Gain (%) =0 ~ 100
05-12: V/F start Frequency =0.00~10.00
1.00-01=18, set the V/F pattern freely complying with 05-04~05-09 (Refer to following diagram)
(V)
05-05
(Vmax)
05-07
(Vmid)
05-09
(Vmin)
Hz
05-08 05-06 05-04 400.00
Figure 4-23 Custom V/F Settings