Chapter 5   Troubleshooting and maintenance 
 5-9  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Any abnormal 
indications? 
 
Replace the current controller
The inverter displays OC, OL 
errors 
Apply power 
Input operation command 
Input frequency command 
 
 
Connect the motor to run 
 
 
The inverter’s output is OK 
Replace I.G.B.T 
Replace faulty circuit board
 
Replace control board 
Replace control board 
Replace control board 
Replace control board 
 
 
Perform detailed chec
 
The inverter is faulted 
O 
O 
YES 
YES
YES
YES 
YES 
YES 
O
O 
O 
O 
O 
NO 
YES 
‧
Is the main circuit 
I.G.B.T workin
 
Any visual abnormalities? 
Is FWD LED 
illuminated? 
Is the output frequency of the 
operating unit displayed? 
Is there  
Voltage at U,V and W output 
terminals? 
Any fault values displayed? 
Is the output current of 
each phase even? 
Is the current detector 
OK?
Is the inverter 
operating well after 
ports replacement? 
YES
YES 
Troubleshooting for OC, OL error displays 
YES 
Figure 5-2 OC, OL Fault Display Flow Chart