4.2 Control Mode Selection 
The N310 Series inverter has two control modes:   
1. V/F Control Mode. 
2. General Vector Control Mode. 
The user can choose these modes with the digital keypad according to the application requirement. 
The factory setting is V/F Control Mode. Before operation, please set the control mode and the 
related motor parameters in accordance with the following flow chart. (The Vector control mode is 
suitable for the motors with the same power rating as the inverter, or one size bigger or smaller if 
necessary). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
※Note:  
1. Use V/F Control Mode: 
(1) Use one inverter to drive several motors simultaneously 
(2) Motor’s nameplate is unknown or motor’s specifications are too special, it will 
cause Auto-tuning fault. 
(3) Specification of inverter and motor differs by more than 1 size. 
2. One inverter drives several motors (Only in V/F mode), set the motor parameters according to the 
following rules: 
(1). Sum the rated current of all motors for total inverter current. 
(2). Input correct VF Pattern parameter (05-04~05-09). 
3. When the nameplate of the motor is unknown, the inverter will be set by default to parameters 
according to the standard TECO motor. 
4. When parameter 00-00=0, the keypad will display ‘Err2’ when performing Auto tuning. 
5. In VECTOR MODE, the max. & min. value of 06-01~06-05 will be limited by one size higher or   
lower than TECO standard motor specification. In VF MODE control, there is no limitation. 
 
End  
Setting procedure for 
control mode 
Control Mode 
V/F Control 
Control mode selection 00-00=0
Set the following parameters: 
V/F Pattern 00-01 
Torque Boost             05-00 
Motor no load current      05-01 (<=06-01) 
Motor Rated Slip 05-02 
Max output frequency      05-04 
Max output voltage        05-05 
Mid output Frequency      05-06 
Mid output voltage         05-07 
Min output frequency      05-08 
Min output voltage        05-09 
Motor Rated Current     06-01 (OL1 reference)
Set the following parameters: 
Motor rated voltage     06-00
Motor rated current      06-01
Motor power  06-02
Motor rated Speed       06-03
Motor rated Frequency     06-04
 
Vector Control 
Perform Auto tuning (06-05=1)
Control mode selection 
00-00=1 
Figure 4-5 Control Mode Selection Chart