Chapter 5   Troubleshooting and maintenance 
 5-7  
 
 
 
O 
N310 INV Fault 
O 
YES 
Is fault known? 
 
Fault signal? 
 
Is the fuse 
intac
?
Replace I.G.B.T 
Replace fuse 
Replace DM 
Check burnt and damaged 
arts 
Visually check controller and  
Drive boards 
 
 
 
Check according to displayed 
fault messa
es 
 
 
 
Apply the power 
Replace the defective boards
 
*to next page 
YES 
YES
YES
O 
O 
O 
O
O
O
O
O
O
 
 
 
Symptoms other than burn 
out, damage, or fuse meltdown in 
the inverter? 
Are displays and 
indicators of the 
operating unit working 
normall
? 
Any fault 
dis
la
? 
3 fault values in 
12-2
YES 
YES
YES
YES
YES
YES
YES
YES
Is the main circuit 
DM intact? 
Is the main circuit 
I.G.B.T intact? 
Is the DC input voltage 
controlling the power 
correct 
Replace control board and 
di
ital o
eratin
 uni
Is the error eliminated 
after replacing control 
board? 
5.3 Quick troubleshooting of N310 
What’s the 
messa
e? 
Any fault 
dis
la
? 
Check 3 fault values of 12-2 with 
▼key. 
Is LED lit? 
Is +5V control 
volta
e correct?
Replace the driver board 
Check terminals and wiring
Replace the pre-charge resistor 
Perform detailed check 
The inverter has faulted 
Any visual abnormalities? 
Any 
 Symptoms of burn 
out and damage?
O 
YES 
z  DM =Diode Mdule 
z  I.G.B.T =Insulat Gate Bipolar Transistor