Chapter 5   Troubleshooting and maintenance 
 5-1  
Chapter 5   Troubleshooting and maintenance 
5.1. Error display and corrective action 
5.1.1. Faults which can not be recovered manually 
Display Fault  Cause  Corrective action 
 
Voltage too high 
when stopped 
Detection circuit malfunction  Return the inverter  
 
Voltage too low 
when stopped 
1.   Power voltage too low 
2.   Pre-charge resistor or fuse 
burnt out. 
3.   Detection circuit malfunction
1.   Check if the power voltage is 
correct  
2.   Replace the pre-charge 
resistor or the fuse 
3.   Return the inverter  
 The inverter is 
overheated 
when stopped 
1.   Detection circuit malfunction
2.   Ambient temperature too high 
or bad ventilation 
1.   Return the inverter  
2.   Improve ventilation 
conditions  
 
Current Sensor 
detection error 
Current sensor error or circuit 
malfunction 
Return the inverter  
 
EEPROM 
problem 
Faulty EEPROM  Replace EEPROM 
 
-OV- 
-LV- 
-OH- 
EPR 
CTER