Chapter 4 Software Index 
4-13 
05-V/F command group 
Function 
Code No. 
Description Range/Code 
Factory 
Setting 
Remarks 
05-00 
Volts/Hz Curve Modification 
(Torque Boost) (%) 
0 ~ 30.0  10.0  *5 
05-01 
Motor No Load Current 
(Amps AC) 
 
----- 
 *5
 
05-02 
Motor rated Slip Compensation 
(%) 
0.0 ~ 100.0  25.0  *5
 
05-03 
v/f max voltage  220V series:170.0 ~ 264.0 
440V series:323.0 ~528.0 
 *5
 
05-04  Maximum Frequency (Hz)  0. 20 ~ 400.00  50.00/60.00  *5 
05-05 
Maximum Frequency Voltage 
Ratio (%) 
0.0 ~ 100.0  100.0 
 
*5
 
05-06  Medium Frequency (Hz)  0. 10 ~ 400.00  25.00/30.00  *5 
05-07 
Medium Frequency Voltage 
Ratio (%) 
 
0.0 ~ 100.0 
 
50.0
 
 
*5 
05-08  Minimum Frequency (Hz)  0. 10 ~ 400.00  0.50/0.60  *5 
05-09 
Minimum Frequency Voltage 
Ratio (%) 
 
0.0 ~ 100.0 
 
1.0
 
*5 
05-10 
 
V/F Energy Saving Mode 
0: Disabled 
1: Controlled by MFIT at Energy Saving 
 
0
 
*5 
05-11  V/F Energy Saving Gain (%)  0 ~ 100  80  *5 
05-12  V/F start Frequency  0.00 ~ 10.00  0.00  *5 
 
06-Motor parameter group 
Function 
Code No. 
Description Range/Code 
Factory 
Setting 
Remarks 
06-00 Motor Rated Voltage (VAC)  -----    *4 
06-01  Motor Rated Current (Amp AC)  -----   *4 
06-02  Motor Rated Power (kW)  -----    *4 
06-03  Motor Rated Speed (RPM)  -----    *4 
06-04  Motor Rated Frequency (Hz)  -----    *4 
06-05 Motor Parameter Auto Tuning 
0:Invalid 
1:Valid 
0  
06-06  Stator Resistance (Ohms)  -----   *3*4 
06-07  Rotor Resistance (Ohms)  -----    *3*4 
06-08  Equivalent Inductance (mH)  -----    *3*4 
06-09 Magnetizing Current (AmpsAC) -----    *3*4 
06-10  Ferrite Loss Conductance (gm)  -----    *3*4 
06-11 
Low-frequency compensation 
Gain 
0 ~ 100  30