Chapter 4 Software Index 
4-21 
4.4 Parameter Function Description 
Group0- The basic parameters group 
 
00-00:Control Mode        0: V/F mode    1: Vector mode (General Purpose)    
To select the appropriate vector control mode or V/F mode according to the load characteristics. 
1. If V/F mode is selected, please set parameters, group5 to comply with the load features. 
Vector is best suited to control the general load or rapidly-changed torque load. 
00-01:Volts/Hz Patterns (V/F)      = 0 ~ 18     
1.00-01= 0~17, V / F Pattern. (Refer to group5) 
2.00-01=18, Flexiable V/F pattern, programmable according to parameters 05-04 ~ 05-09. 
00-03: Main Run Command Source Select 
=0 : Keypad   
=1 : External Run/Stop Control 
=2 : Communication 
          =3 : Expansion card (Reserved) 
00-04: Alternative Run Command Source Select 
=0 : Keypad   
=1 : External Run/Stop Control 
=2 : Communication 
=3 : Expansion card (Reserved) 
1. 00-03/00-04=0, the inverter is controlled by the keypad. 
2. 00-03/00-04=1, the inverter is controlled by the external terminals, and the Stop key for emergency 
stop is operational.    (Refer to 04-02 description) 
※Note:00-03/00-04=1, please refer to parameter 04-03, 04-04, 04-06, 04-07 for detailed description in 
order to ensure safety of operators and machines. 
3. 00-03/00-04=2, the inverter is controlled by Communication. 
4. 00-03/00-04=3, the inverter is controlled by expansion card.(Reserved). 
5. When 01-00 ~ 01-05 is set 13(Main/Alt Control Signal Select), if the terminal is ON, the inverter is 
controlled by parameter 00-03, if the terminal is Off, the inverter is controlled by parameter 
00-04. 
00-05: Main Frequency Command Source Select 
=0 : UP/DOWN of Keypad 
=1 : Potentiometer on Keypad 
=2 : External AI1 Analog Signal Input 
=3 : External Up/Down Frequency Control 
=4 : Communication setting Frequency 
00-06: Alternative Frequency Command Source Select 
=0 : UP/DOWN of Keypad 
=1 : Potentiometer on Keypad 
=2 : External AI1 Analog Signal Input 
=3 : External Up/Down Frequency Control 
=4 : Communication setting Frequency 
1.Please refer to description of parameter group 01-00  ~  01-05 (multifunction input terminals) for 
the function Up/Down terminal.