Chapter 4 Software Index 
4-58 
 
(C) Auto_Run Mode for Single Cycle (13-00 = 3, 6) 
The speed of final step will be held to run. 
For example: 
13-00 = 3 (or 6)       
Panel Frequency (3-01) =15 Hz   13-01=30Hz     13-02=50Hz  13-15=20Hz 
13-16=20s      13-17=25s     13-18=30s   13-31=40s 
13-32=1        13-33=1       13-34 = 1   13-47=1(FWD)   
13-04~13-15=0Hz  , 13-20 ~ 13-30=0s  ,   13-35 ~ 13-46 = 0  
 
 
 
 
 
Note:13-00 = 1~3 : If the inverter stops and re-starts, it will continue running from the unfinished 
step, according to the setting of 13-00. 
= 4~6: If the inverter stops and re-starts, it will begin a new cycle and continue running 
according to the setting of 13-00. 
 
13-00 
1~3 4~6 
Output Frequency 
time
Output
Frequency
Run
Command
Continue running from
 unfinished step
stop runrun
time
Output
Frequency
Run
Command
begin a new cycle
stop runrun
 
●ACC/DEC time follow the setting of 00-09/00-10 or 10-05/10-06 in Auto Run Mode.
 
Note: Auto _ Run Mode Frequency Command 0 =3-01(Keypad Freq) 
Figure 4-31 Single cycle auto run: final step hold 
Figure 4-32 AUTO_RUN cycle with interrupt