Chapter 4 Software Index 
4-15 
07-09 
Over torque Detection Selection 
(OL3) 
0: Disable Over torque Operation 
1: Enable Over torque Operation   
Only if at Set Frequency 
2: Enable Over torque Operation   
while the Drive is in Run Mode 
0   
07-10 
Operation After Over torque 
Detection is Activated 
0: Coast-to-Stop After Over   
torque is Activated   
1: Drive will Continue to   
Operate After Over torque is 
Activated  (OL3) 
1   
07-11 
Over torque Threshold Level 
(%) 
30 ~ 300  160   
07-12 
Over torque Activation Delay 
Time (Seconds) 
0.0 ~ 25.0  0.1   
07-13 
OH over heat Protection
 ( cooling 
fan control)
  
0: Auto (Depends on temp.) 
1: Operate while in RUN mode 
2: Always Run 
3: Disabled 
1  
 
 
08-Communication function group 
Function 
Code No. 
Description Range/Code 
Factory 
Setting 
Remarks 
08-00 
Assigned Communication 
Station Number 
0~ 32  1  *2*4 
08-01  RTU code /ASCII code select 
0:RTU code 
1:ASCII code 
0 *2*3 
08-02  Baud Rate Setting (bps) 
0:4800 
1:9600 
2:19200 
3:38400 
2 *2*3 
08-03  Stop Bit Selection 
0:1 Stop Bit     
1:2 Stop Bits   
0 *2*3 
08-04 Parity Selection 
0:Without Parity 
1:With Even Parity 
2:With Odd Parity 
0 *2*3 
08-05  Data Format Selection 
0: 8-Bits Data   
1: 7-Bits Data 
0 *2*3 
08-06 
Communication time-out   
detection time 
0.0 ~ 25.5  0.0   
08-07 
Communication time-out   
operation selection 
0:Deceleration to stop 
(00-10: Deceleration time 1) 
1:Coast to stop 
2: Deceleration to stop 
(10-06: Deceleration time 2) 
3: continue operating 
0  
08-08  Err6 fault tolerance times  1 ~ 20  3   
08-09  Drive Transmit Wait Time(ms) 5 ~ 65  5