Chapter 4 Software Index
4-15
07-09
Over torque Detection Selection
(OL3)
0: Disable Over torque Operation
1: Enable Over torque Operation
Only if at Set Frequency
2: Enable Over torque Operation
while the Drive is in Run Mode
0
07-10
Operation After Over torque
Detection is Activated
0: Coast-to-Stop After Over
torque is Activated
1: Drive will Continue to
Operate After Over torque is
Activated (OL3)
1
07-11
Over torque Threshold Level
(%)
30 ~ 300 160
07-12
Over torque Activation Delay
Time (Seconds)
0.0 ~ 25.0 0.1
07-13
OH over heat Protection
( cooling
fan control)
0: Auto (Depends on temp.)
1: Operate while in RUN mode
2: Always Run
3: Disabled
1
08-Communication function group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
08-00
Assigned Communication
Station Number
0~ 32 1 *2*4
08-01 RTU code /ASCII code select
0:RTU code
1:ASCII code
0 *2*3
08-02 Baud Rate Setting (bps)
0:4800
1:9600
2:19200
3:38400
2 *2*3
08-03 Stop Bit Selection
0:1 Stop Bit
1:2 Stop Bits
0 *2*3
08-04 Parity Selection
0:Without Parity
1:With Even Parity
2:With Odd Parity
0 *2*3
08-05 Data Format Selection
0: 8-Bits Data
1: 7-Bits Data
0 *2*3
08-06
Communication time-out
detection time
0.0 ~ 25.5 0.0
08-07
Communication time-out
operation selection
0:Deceleration to stop
(00-10: Deceleration time 1)
1:Coast to stop
2: Deceleration to stop
(10-06: Deceleration time 2)
3: continue operating
0
08-08 Err6 fault tolerance times 1 ~ 20 3
08-09 Drive Transmit Wait Timems 5 ~ 65 5