Chapter 4 Software Index
4-24
Note: 1.As 3 wire control mode is selected, the terminal S1, S2 and S3 is not controlled
by 01-00, 01-01 and 01-02.
2. 10-01=1, the reverse command is unavailable.
00-12: Jog Frequency (Hz) =1.00 25.00
00-13: Jog Acceleration Time (MFIT) (Seconds) =0.1~25.5
00-14: Jog Deceleration Time (MFIT) (Seconds) =0.1~ 25.5
ExampleWhen 1-00(S1)=61-01(S2)=7 (Jog), Jog run is controlled by external terminals, S1 on is
Jog-forward, S2 on is Jog-reverse.
Group1- External terminal digital signal input function group
Multifunction input terminals (TM2 S1-S6) controlling:
01-00~05:
0:Forward/Stop Command
1:Reverse/Stop Command
2: Preset Speed unit 0 (3-02)
3: Preset Speed unit 1 (3-03)
4: Preset Speed unit 2 (3-05)
5: Preset Speed unit 3 (3-09)
6:JOG Forward Command
7:JOG Reverse Command
8:Acc/Dec time 2
9:Emergency Stop
10:Base Block
11:Speed Search
12:Energy Saving(V/F)
Figure 4-9 Drive start/stop operation sequences