Chapter 4 Software Index 
4-8 
00-06 
Subsidiary Frequency 
Command Source Selection 
0:
 Keypad 
1: Potentiometer on Keypad 
2:
 External AI1 Analog Signal Input   
3:
 External Up/Down Frequency Control   
4: Communication setting Frequency 
0  
00-07  Frequency Upper Limit (Hz)  0.01~400.00  50.00/60.00  
00-08  Frequency Lower Limit (Hz)  0.01~399.99  0.00   
00-09 Acceleration Time 1(Seconds) 0.1~3600.0  10.0  *1 
00-10 Deceleration Time 1(Seconds) 0.1~3600.0  10.0  *1 
00-11 
Operation modes for external 
terminals 
0: Forward/Stop-Reverse/Stop 
1: Run/Stop-Forward/Reverse 
2: 3-Wire Control Mode-Run/Stop 
0  
00-12 Jog Frequency (Hz)  1.00~25.00  2.00  *1 
00-13 
Jog Acceleration Time (MFIT) 
(Seconds) 
0.1~25.5 0.5 *1 
00-14 
Jog Deceleration Time (MFIT) 
(Seconds) 
0.1~25.5 0.5 *1 
 
 
1- External terminal digital signal input function group 
Function 
Code No. 
Description Range/Code 
Factory 
Setting 
Remarks
01-00  Multifunction Input Term. S1  0   
01-01  Multifunction Input Term. S2  1   
01-02  Multifunction Input Term. S3  2   
01-03  Multifunction Input Term. S4  3   
01-04  Multifunction Input Term. S5  4   
01-05  Multifunction Input Term. S6 
0: Forward/Stop Command   
1: Reverse/Stop Command     
2: Preset Speed unit    0 (3-02)   
3: Preset Speed unit    1 (3-03) 
4: Preset Speed unit    2 (3-05) 
5: Preset Speed unit    3 (3-09) 
6: Jog Forward Command 
7: Jog Reverse Command 
8:
 Acc/Dec 2 
9: Emergency Stop 
10:
 Base Block 
11:
 Speed Search 
12: Energy Saving (V/F) 
13:Main/Alt run Command select 
14: Acc/Dec Disabled 
15:
 Up Command 
16:
 Down Command 
17: Main/Alt Frequency Command select 
18:
 PID Function Disabled 
19:
 Integration Value Resets to Zero 
20:
 Reset 
21:KEB function 
22: Auto _ Run Mode 
20  
01-06 
Multifunction terminal S1~ S6 confirm 
the scan times 
1~ 200 (mSec X 2 )  10   
01-07  Up/Down (Hz) 0.00~ 5.00  0.00