EasyManua.ls Logo

TECO N310 Series - Auto Restart Method; Delay-ON Timer (Seconds); Direct Running after Power up; Reset Mode Setting

TECO N310 Series
111 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Software Index
4-38
04-05 : Auto Restart Method:
=0: Enable Speed Search
=1: Normal Start
1. 04-05=0: When auto-restarting the inverter will detect the rotating speed of the motor. The Motor
will be controlled to accelerate from the present speed to the target speed.
2. 04-05=1: The inverter restart from 0 speed to set frequency in acceleration time when auto-restart.
04-06 : Auto Restart Delay Time (Seconds):0 ~ 800.0 second
04-07 : Number of Auto Restart Attempts: 0 ~ 10 times
1. 04-07=0: The inverter will not auto restart after trips due to fault.
2. 04-07>0, 04-06= 0:
The inverter will conduct SPIN START in 0.5 second after trips due to fault. The motor will
Coast to stop while the output is switched off, Once the rotating speed is determined then it will
accelerate or decelerate from this speed to the running speed before the fault.
3. 04-07>0, 04-06>0:
The output will be stopped for a period which is determined by the 04-06 after a fault trip. Then, spin
start to set target frequency.
4. Auto restart after a fault will not function while DC injection braking or decelerating to stop.
04-08: Reset Mode Setting
0: Enable Reset Only when Run Command is Off
1: Enable Reset when Run Command is On or Off
04-08=0 Once the inverter is detected a fault, please turn Run switch Off and then On again to
perform reset, otherwise restarting will not be possible.
04-09: Direct Running After Power Up
0: Enable Direct running after power up 1: Disable Direct running after power up
Danger
1. 04-09=0 and the inverter is set external terminal controlled00-03/00-04=1, if the run switch is
ON as power is supplied, the inverter will auto start. It is recommend that the power is turned off and
the run switch is also off to avoid possibility of injury to operators and machines as the power is
reapplied.
Note: IF this mode is required all safety measures must be considered including warning labels.
2. 04-09=1and the inverter is set external terminal controlled00-03/00-04=1, if the run switch is
ON as power is supplied, the inverter will not auto start and the display will flash with STP1.
It is necessary to turn OFF the run switch and then ON to start normally.
04-10: Delay-ON Timer (Seconds): 1.8 ~ 300.0 second
As power on and 04-09=0, the inverter will perform auto restart in the setting time for delay.
04-11: Kinetic Energy Back-up Deceleration Time (S)
= 0.0: Disable = 0.1~25.0 : KEB Deceleration Time
04-11 = 0 KEB function disable 04-11 0 KEB function enables
Example : 220V system

Table of Contents

Related product manuals