Chapter 4 Software Index
4-9
01-08 Up/Down keep Frequency mode
0:
When Up/Down is used, the preset
frequency is held as the inverter stops,
and the UP/Down function is disabled.
1: When Up/Down is used, the preset
frequency is reset to 0 Hz as the
inverter stops.
2: When Up/Down is used, the preset
frequency is held as the inverter stops,
and the UP/Down is available
.
0
01-09 Output Relay RY1 Operation Mode 1
01-10 Output Relay TR1 Operation Mode
0: Run
1: Fault
2: Frequency Reached
3: Set Frequency
4: Frequency Threshold Level
(> 1-11) - Frequency Reached
5: Frequency Threshold Level
(< 1-11) - Frequency Reached
6: Auto Restart
7: Momentary AC Power Loss
8: Emergency Stop Mode
9:
Base Block Stop Mode
10: Motor Overload Protection(OL1)
11: Drive Overload Protection(OL2)
12: Over torque Threshold Level(OL3)
13: PID Feedback Signal Loss
0
01-11 Frequency Output Setting (Hz) 0.00 ~ 400.00 0.00 *1
01-12 Frequency Detection Range 0.00 ~ 30.00 2.00 *1
01-13 S1~ S5 switch type select
xxxx0: S1 NO xxxx1: S1 NC
xxx0x: S2 NO xxx1x: S2 NC
xx0xx: S3 NO xx1xx: S3 NC
x0xxx: S4 NO x1xxx: S4 NC
0xxxx: S5 NO 1xxxx: S5 NC
00000
01-14 S6 switch type select
xxxx0: S6 NO
xxxx1: S6 NC
00000
“NO”: Normal open, “NC”: Normal close.
2- External terminal analog signal input function group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
setting AI1 AI2
0 0~10V (or 0~20mA) 0~10V (or 0~20mA)
1 0~10V (or 0~20mA) 2~10V (or 4~20mA)
2 2~10V (or 4~20mA) 0~10V (or 0~20mA)
02-00
AI1/AI2 analog Input signal type
select
3 2~10V (or 4~20mA) 2~10V (or 4~20mA)
0
02-01 AI1 Signal Verification Scan 1 ~ 200(mSec × 2) 100
02-02 AI1 Gain (%) 0 ~1000 100 *1
02-03 AI1 Bias (%) 0.0 ~100.0 0.0 *1
02-04 AI1 Bias Selection
0: Positive
1: Negative
0 *1