Chapter 4 Software Index
4-28
17. 01-00~05=21 (Power Source Detect for KEB)
Refer to 04-11.
18. 01-00~05=22(Auto _ Run Mode)
AUTO_RUN function is simple built-in PLC function, set external terminals function as
22,turn it on ,and set parameter in group 13,AUTO_RUN function is set completly, refer to
group 13.
Digital /Analog input signal scan times:
01-06: Multifunction terminal S1S6 confirm the scan times (mSec X 2),1~200 times
1. TM2 terminal is used for scanning. If there are the same signals continuously input for N times, the
inverter will treat the signal as normal. During the signal evaluation, if the scan times are less than N,
the signal will be treated as noise.
2. Each scan period is 2ms.
3. The user can specify the scan times interval duration according to the noise environment. If the
noise is serious, increase the value of 01-06, however the response will be slower.
Step of Up/Down Function (Hz):
01-07: Up/Down (Hz) 0.00 ~ 5.00
There are two modes covered below:
1 .01-07 = 0.00, the operation is just as the original one. When the UP terminal is ON, the frequency
increases while the DOWN terminal is ON, the frequency decreases. (Refer to the following
graph).
2. 01-07 = 0.01 to 5.00, and UP/ DOWN terminal ON, is equivalent to a step increase/ decrease at
the increment frequency in 01-07. If UP/DOWN is pressed over 2 seconds, the original
UP/DOWN mode is restored (Please refer to the following diagram)
Figure 4-12 UP/DOWN original mode example