Chapter 4 Software Index
4-17
10-Assistant function group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
10-00 Expansion card type Reserved
10-01 Reverse operation control
0: Reverse command is enabled
1: Reverse command is disabled
0
10-02
Keypad Operation with
Up/Down Keys in Run Mode
0: ‘Enter’ must be pressed after
Frequency change with Up/Down Keys
on keypad.
1: Frequency will be changed
directly when Up/Down Keys
are Pressed
0
10-03 Carrier Frequency (kHz) 1~ 15 5
10-04 Carrier mode Selection
0: Carrier mode0
3-phase PW M modulation
1: Carrier mode1
2-phase PW M modulation
2: Carrier mode2
2-phase randomized PW M modulation
3: Carrier mode3
randomized PW M modulation
4: Carrier mode4
dual randomized PW M modulation
1
10-05
Acceleration Time 2 (MFIT)
(Seconds)
0.1 ~ 3600.0 10.0 *1
10-06
Deceleration Time 2 (MFIT)
(Seconds)
0.1 ~ 3600.0 10.0 *1
10-07 S-Curve Acc/Dec 1 (Seconds) 0.0 ~ 4.0 0.2
10-08 S-Curve Acc/Dec 2(Seconds) 0.0 ~ 4.0 0.2
10-09 S-Curve Acc/Dec 3 (Seconds) 0.0 ~ 4.0 0.2
10-10 S-Curve Acc/Dec 4 (Seconds) 0.0 ~ 4.0 0.2
10-11 Skip Frequency 1 (Hz) 0.00 ~ 400.00 0.00 *1
10-12 Skip Frequency 2 (Hz) 0.00 ~ 400.00 0.00 *1
10-13 Skip Frequency 3 (Hz) 0.00 ~ 400.00 0.00 *1
10-14 Skip Frequency Bandwidth (±Hz) 0.00 ~ 30.00 0.00 *1
10-15
Carrier Frequency
Reduction by temperature raising
0:disabled
1:enabled
0