Chapter 4 Software Index 
4-10 
02-05 AI1 Slope 
0: Positive 
1: Negative 
0 *1 
02-06 AI2 function Select 
0:
 PID feedback signal 
1: AI2 Bias signal input 
0  
02-07  AI2 Signal Verification Scan  1 ~ 200(mSec × 2)  100   
02-08  AI2 Gain (%)  0 ~1000  100  *1 
02-09  AI2 Bias (%)  0.0 ~100.0  0.0  *1 
02-10 AI2 Bias Selection 
0: Positive 
1: Negative 
0 *1 
02-11 AI2 Slope 
0: Positive 
1: Negative 
0 *1 
02-12  Analog Output Mode(FM+) 
0: Output Frequency   
1: Frequency Setting 
2: Output Voltage 
3: DC Bus Voltage 
4: Motor Current 
0 *1 
02-13  Analog Output FM+ Gain (%)  0 ~1000  100  *1 
02-14  Analog Output FM+ Bias (%)  0.0 ~100.0  0.0  *1 
02-15  FM+ Bias Selection 
0: Positive 
1: Negative 
0 *1 
02-16 FM+ Slope 
0: Positive 
1: Negative 
0 *1 
 
3-preset Frequency function group 
Function 
Code No. 
Description Range/Code 
Factory
Setting 
Remarks
03-00 
Preset Speed Control mode 
Selection 
0: common 
(Is uniform time( Acc1/Dec1or Acc2/Dec2) 
1: special 
(is single time Acc0/Dec0~ Acc15/Dec15) 
0   
03-01  Preset Speed 0  (Hz)   0.00 ~ 400.00  5.00  Keypad Freq
03-02  Preset Speed1    (Hz)  0.00 ~ 400.00  5.00  *1 
03-03  Preset Speed2    (Hz)  0.00 ~ 400.00  10.00 
*1
 
03-04  Preset Speed3    (Hz)  0.00 ~ 400.00  15.00 
*1
 
03-05  Preset Speed4    (Hz)  0.00 ~ 400.00  20.00 
*1
 
03-06  Preset Speed5    (Hz)  0.00 ~ 400.00  25.00 
*1
 
03-07  Preset Speed6    (Hz)  0.00 ~ 400.00  30.00 
*1
 
03-08  Preset Speed7    (Hz)  0.00 ~ 400.00  35.00 
*1
 
03-09  Preset Speed8    (Hz)  0.00 ~ 400.00  40.00 
*1
 
03-10  Preset Speed9    (Hz)  0.00 ~ 400.00  45.00 
*1
 
03-11  Preset Speed10    (Hz)  0.00 ~ 400.00  50.00 
*1