Chapter 4 Software Index
4-57
Some examples in auto_run mode as follows:
(A) Single Cycle Running (13-00= 1, 4)
The inverter will run for a single full cycle based upon the specified setting mode. Then, it
will stop.
For example:
13-00=1 (or 4)
Panel Frequency (3-01)=15 Hz 13-01=30Hz 13-02=50Hz 13-03=20Hz
13-16=20s 13-17=25s 13-18=30s 13-19=40s
13-32=1 13-33=1 13-34=1(FWD) 13-35=2(REV)
13-0413-15=0Hz , 13-2013-31=0s , 13-3613-47=0
(B) Periodic cycle Running (13-002, 5)
The inverter will repeat the same cycle periodically.
For example:
13-00=2 (or 5)
13-01~13-1513-16~13-3113-32~13-47 : Same setting as the example (A)
Figure 4-29 Single cycle auto run
Figure 4-30 Periodic cycle auto run