Chapter 5   Troubleshooting and maintenance 
 5-4  
 
5.1.2. Special conditions 
Display Fault  Description 
 
Zero speed  at stop 
 
Occurs when preset frequency <0.1Hz 
 
 
 
Fail to start directly 
On power up. 
1.   If the inverter is set for external terminal control mode 
      (00-03/00-04=1) and direct start is disabled (04-09=1) 
      The inverter cannot be started and will flash STP1. 
 
The run input is active at power-up, refer to descriptions of (04-09). 
2.   Direct start is possible when 04-09=0. 
 
Keypad Stop 
Operated 
when inverter 
in external 
Control mode. 
1.   With the  function of Stop key enabled by (04-02=0) 
      And if the Stop key is pressed while the inverter is set to external 
control mode (00-03/00-04=1) then, the inverter will stop according 
to the setting of 04-01 and the error message, ‘STP2’flashes after 
stop.  
      Release and re-activate the run contact to restart the inverter. 
2.   If the inverter is in communication mode and the Stop key is enabled 
(04-02=0), the inverter will stop in the way set by 04-01 when Stop 
key is pressed during operation and then flashes STP2. The Host 
controller has to send a Stop command then a Run command to the 
inverter for it to be restarted. 
3.   Stop key will be disabled when  04-02=1  
 
External 
Rapid stop 
The inverter will decelerate to stop and then flash E.S., when input 
external Rapid stop signal via the multifunctional input terminal 
activates (refer to descriptions of 01-00~01-05). 
 
External base 
block 
The inverter stops immediately and then flashes b.b., when external 
base block is input by the multifunctional input terminals. 
(Refer to descriptions of 01-00~01-05). 
 
 
Auto-tuning faults 
1.   Motor data error resulting in auto-tuning failure 
2.   Stopping the inverter during Auto-tuning before completion 
 
PID feedback loss  PID feedback loss detect 
 
Communication 
error 
Communication  error detect (refer  group 8 ) 
 
STP2 
b.b. 
STP1 
STP0 
ATER 
PDER 
E.S. 
COT