Chapter 4 Software Index
4-14
07-Protection function group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
07-00 Trip Prevention Selection
xxxx0:
Enable Trip Prevention During
Acceleration
xxxx1:
Disable Trip Prevention During
Acceleration
xxx0x:
Enable Trip Prevention During
Deceleration
xxx1x:
Disable Trip Prevention During
Deceleration
xx0xx:
Enable Trip Prevention in Run
Mode
xx1xx:
Disable Trip Prevention in
Run Mode
x0xxx: Enable over voltage Prevention
in Run Mode
x1xxx: Disable over voltage Prevention
in Run Mode
00000
07-01
Trip Prevention Level During
Acceleration (%)
50 ~ 200 200
Inverter Rated
Current
200%
07-02
Trip Prevention Level During
Deceleration (%)
50 ~ 200 200
Inverter Rated
Current
200%
07-03
Trip Prevention Level In Run
Mode (%)
50 ~ 200 200
Inverter Rated
Current
200%
07-04
over voltage Prevention Level in
Run Mode
350.0 VDC ~ 390.0 VDC
700.0 VDC ~ 780.0 VDC
380.0/760.0
07-05
Electronic Motor Overload
Protection Operation Mode
0: Enable Electronic Motor
Overload Protection
1: Disable Electronic Motor
Overload Protection
1
07-06 Motor type Selection
0: Electronic Motor Overload
Protection Set for
Non-Inverter Duty Motor
1: Electronic Motor Overload
Protection Set for Inverter
Duty Motor
0
07-07
Motor Overload Protection
Curve Selection
0: Constant Torque (OL =103 %)
(150 % for 1 Minute)
1:
Variable Torque (OL = 113 %)
(123 % for 1 Minute)
0
07-08
Operation After Overload
Protection is Activated
0: Coast-to-Stop After Overload
Protection is Activated
1: Drive Will Not Trip when Overload
Protection is
Activated (OL1)
0

Table of Contents