Chapter 4 Software Index 
4-34 
1)  The inverter reads the average value of A/D signals once per (02-01/02-07 x 2mS). Set scan 
intervals according to possible noise interference in the environment. Increase 02-01/02-07 in an 
environment with noise interference, but the response time will increase accordingly. 
Multifunction analog output control   
02-12:  Analog Output Voltage Mode    
0: Output frequency 
1: Frequency Setting 
2: Output voltage 
3: DC Bus Voltage 
4: Output current 
02-13:    FM+ Gain(%) 0 - 1000 
02-14:    FM+ Bias(%) 0 .0- 100.0 
02-15:  FM+ Bias Selection   0:positive   1:Negative 
02-16:  FM+ Slope          0:positive   1:Negative 
1. The multifunction analog output terminal of the terminal block (TM2), is 0~10Vdc analog output. 
The output type is determined by the02-12. The output voltage level can be scaled by parameter 
02-13 to suit external meters and peripherals. 
Note: the max output voltage is 10V due to hardware of the circuit. Use only devices that require a 
maximum of 10V signal. 
2. FM+ Function Description 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Note:02-13~02-16 ,refer to Figure 4-19 Analog scaling examples. 
 
 
 
 
 
 
 
 
0 
10V 
2-12=0 Output Frequency        Xmax= upper frequency limit   
=1 frequency setting               upper frequency limit   
=2 Output Voltage              Motor Rated Voltage (VAC) 
=3 DC Bus Voltage                220V:0~400V 
440V:0~800V 
=4 Motor Current           2 times rated current of inverter 
Xmax 
Figure 4-20 Multifunction analog output