Chapter 5   Troubleshooting and maintenance 
 5-3  
3. Faults which can be recovered manually but not automatically 
Display Fault  Cause  Corrective Action 
 
Over-current during 
stop 
 
1. Detection circuit 
malfunction 
2. Bad connection for CT 
signal cable 
1.Check the noise between Power 
line and motor line 
2.Return the inverter for repair 
 
Motor overload 
1. Excessive load 
2. Incorrect settings for 
    06-01, 07-05~08 
1. Increase the motor capacity 
2. set 06-01, 07-05~08 correctly 
  Inverter overload  Excessive Load 
Increase the inverter capacity 
 
 Over torque 
1. Excessive Load 
2. Incorrect settings for 
     07-11, 07-12 
1. Increase the inverter capacity 
2. set 07-11, 07-12 correctly 
 
Voltage too low 
during operation 
1. Power voltage too low 
2. Power voltage varies widely
   (fluctuates) 
1. Improve power quality or 
increase the value of 4-04 
2. Set a longer acceleration time 
3. Add a reactor at the power input 
side 
4. Increase the motor capacity 
 
 
 
 
 
 
 
 
 
 
 
 
 
OL1 
OL2 
OL3 
OC 
LV-C