Chapter 5   Troubleshooting and maintenance 
 5-5  
5.1.3. Operation errors  
 
Display 
Error 
Cause Corrective Action 
 Parameter and 
frequency 
reverse already 
locked 
1.Attempt to modify frequency 
parameter while 12-07>0 
2.Attempt to reverse while 
 10-01=1 
1. Set 12-07=0 
2. Set 10-01=0 
 
Keypad
 
operation error 
 
1. Press ▲ or ▼while 00-05/00-
06>0 or running at preset 
speed. 
2. Attempt to modify the Parameter. 
Can not be modified during operation 
(refer to the parameter list). 
1.The ▲ or▼ is available 
for modifying the 
parameter only when 
00-05/00-06=0 
2. Modify the parameter 
in STOP mode. 
 
 
 
Parameter setting 
error  
1. 00-08 is within the range of 
    10-11 ± 10-14 or 10-12 ± 10-14 or 
    10-13 ± 10-14 
2. 00-07≤00-08 
   3.Setting error while 
      Performing Auto tuning. 
   (e.g.00-03/00-04≠0,00-05/00-06 ≠ 0 ) 
1. Modify 10-11~10-13 or 
 10-14 
2. Set  00-07>00-08 
3. Set  00-03/00-04=0 and     
        05/00-06=0, 
        during Auto tuning 
 
Modification of 
parameter is 
not available in 
communication 
1. Control command sent during 
communication. 
2. Attempt to modify the function 
08-02 ~ 08-05 during 
communication  
1. Issue enable command 
before communication 
2. Set parameters           
08-02 ~ 08-05 function 
before  communication 
 
 
 
 
Communication 
failed 
 
1. Wiring error 
2. Communication parameter setting 
error. 
3. Check-Sum error 
4. Incorrect communication protocol 
1.Check hardware and wiring 
2.Check Functions               
08-02 ~ 08-05 
 
 
 
 
 
Parameter 
conflict 
 
1. Attempt to modify the function 12-
00/12-06. 
2. Voltage and current detection circuit 
is abnormal 
If Reset is not possible, 
please Return the inverter 
LOC 
Err1 
Err2 
Err5 
Err6 
Err7