Chapter 5 Troubleshooting and maintenance
5-5
5.1.3. Operation errors
Display
Error
Cause Corrective Action
Parameter and
frequency
reverse already
locked
1.Attempt to modify frequency
parameter while 12-07>0
2.Attempt to reverse while
10-01=1
1. Set 12-07=0
2. Set 10-01=0
Keypad
operation error
1. Press or while 00-05/00-
06>0 or running at preset
speed.
2. Attempt to modify the Parameter.
Can not be modified during operation
(refer to the parameter list).
1.The or is available
for modifying the
parameter only when
00-05/00-06=0
2. Modify the parameter
in STOP mode.
Parameter setting
error
1. 00-08 is within the range of
10-11 ± 10-14 or 10-12 ± 10-14 or
10-13 ± 10-14
2. 00-0700-08
3.Setting error while
Performing Auto tuning.
(e.g.00-03/00-040,00-05/00-06 0 )
1. Modify 10-11~10-13 or
10-14
2. Set 00-07>00-08
3. Set 00-03/00-04=0 and
05/00-06=0,
during Auto tuning
Modification of
parameter is
not available in
communication
1. Control command sent during
communication.
2. Attempt to modify the function
08-02 ~ 08-05 during
communication
1. Issue enable command
before communication
2. Set parameters
08-02 ~ 08-05 function
before communication
Communication
failed
1. Wiring error
2. Communication parameter setting
error.
3. Check-Sum error
4. Incorrect communication protocol
1.Check hardware and wiring
2.Check Functions
08-02 ~ 08-05
Parameter
conflict
1. Attempt to modify the function 12-
00/12-06.
2. Voltage and current detection circuit
is abnormal
If Reset is not possible,
please Return the inverter
LOC
Err1
Err2
Err5
Err6
Err7

Table of Contents