Chapter 3   Ambient Environment and Installation 
3-9 
3.4 Specifications 
3.4.1 Product Specifications 
 Single / Three phase, 200-240V model  
N310-□□□□-XXX  20P5  2001  2002  2003 
Horsepower(HP) 0.5 1 2 3 
Max Applicable Motor Output (KW)  0.4  0.75  1.5  2.2 
Rated Output Current(A)  3.1  4.5  7.5  10.5 
Rated Capacity(KVA)  1.2  1.7  2.9  4.0 
Max. Input Voltage  
Single/Three Phase: 200~240V +10% -15%,50/60H
Z 
±  5% 
Max. Output Voltage  Three  Phase:  200~240V 
Input Current(A)  8.5/4.5  12/6.5  16/11  23.9/12.5 
Net Weight (KG)  1.4  1.4  2.5  4.0 
Allowable momentary power loss 
time (second) 
1.0   1.0  2.0  2.0 
Three phase, 380 – 480V model 
N310-□□□□-XXX 
4001 4002 4003 4005 4008 4010 4015       
Horsepower(HP)  1 2 3 5 7.5 10 15    
Max Applicable Motor Output (KW)  0.75 1.5 2.2 3.7 5.5 7.5 11       
Rated Output Current(A)  2.3 3.8 5.2 8.8 13.0 17.5 25       
Rated Capacity(KVA)  1.7 2.9 4.0 6.7 9.9 13.3 19.1      
Max. Input Voltage 
Three phase 380~480V +10%-15%,50/60H
Z 
±  5% 
Max. Output Voltage 
Three phase 380~480V 
Input Current(A)  4.2 5.6 7.3 11.6 17  23 31       
Net Weight (KG)  2.4 2.5 3.8 4.0 4.0 7.0 7.0      
Allowable momentary power loss 
time (second) 
1.0 1.0 2.0 2.0 2.0 2.0 2.0