Chapter 3   Ambient Environment and Installation 
3-6 
3.3.3 Precautions for peripheral applications: 
 
 
 
Power supply: 
z  Make sure the correct voltage is applied to avoid 
damaging the inverter. 
z  A molded-case circuit breaker or fused disconnect 
must be installed between the AC source and the 
inverter 
Molded-case circuit breaker:  
z  Use a molded-case circuit breaker that conforms to the 
rated voltage and current of the inverter to control the 
power ON/OFF and protect the inverter. 
z  Do not use the circuit breaker as the run/stop switch 
for the inverter. 
Leakage breaker:  
z  Install a leakage breaker to prevent problems caused 
by electric leakage and to protect personnel. 
z  Setting current should be 200mA or above and the 
operating time at 0.1 second or longer to prevent 
malfunctions. 
Magnetic contactor:  
z  Normal operations do not need a magnetic contactor. 
However a contactor has to be installed in primary 
side when performing functions such as external 
control and auto restart after power failure, or when 
using a brake controller.  
z  Do not use the magnetic contactor as the run/stop 
switch of the inverter. 
AC reactor for power quality improvement: 
z  When inverters below 200V/400V class 15KW are 
supplied with high capacity (above 600KVA) power 
source or an AC reactor can be connected to improve 
the power performance. 
Install fast action fuse: 
z  To ensure the safety of peripheral devices, please 
install fast action fuse. Regarding the specification, 
please refer to P3-4. 
Input noise filter:  
z  A filter must be installed when there are inductive 
loads affecting the inverter 
Inverter:  
z  Input power terminals L1, L2, and L3 can be used in 
any sequence regardless of phase. 
z  Output terminals T1, T2, and T3 are connected to U, 
V, and W terminals of the motor. If the motor is 
reversed while the inverter is set to run forward, just 
swap any two terminals of T1, T2, and T3. 
z  To avoid damaging the inverter, do not connect the 
input terminals T1, T2, and T3 to AC input power. 
z  Connect the ground terminal properly. 200V class: 
class 3 grounding, <100Ω; 400V class : <10Ω. 
Figure 3-3 Typical Installation Schematic