Chapter 3   Ambient Environment and Installation 
3-11 
 
Item N310 TYPE 
Communication Control 
1.  Control by RS232 or RS485  
2.  One to one or one to many (RS485 ONLY) control. 
3.  BAUD RATE/STOP BIT/PARITY/bit can be set 
Braking Torque 
About 20﹪, the model below 20HP with built-in braking 
transistor and the specified  external braking resistors can 
provide 100%  
Operation temperature 
14-120℉(-10 ~ 50℃) 
Storage temperature 
4-140℉(-20 ~ 60℃) 
Humidity 
0 – 95% Relative Humidity(Non-condense) 
Vibration  
1G (9.8m/ 
2
S  ) 
Enclosure 
IP20  
Overload protection 
The relays to protect the motor (the curve can be set) and the 
inverter (150 % / 1min)  
Over Voltage 
200V class: DC Voltage>410V 400Vclass: DC Voltage>820V
Under Voltage 
200V class: DC Voltage
<190V 400Vclass: DC Voltage<380V
Momentary Power 
Loss Restart 
Restart can be initiated with spin start after momentary power 
loss in Max 2 sec. 
Stall Prevention 
Stall prevention for Acceleration/ Deceleration/ Operation. 
Short-circuit output 
terminal 
Electronic Circuit Protection 
Grounding Fault 
Electronic Circuit Protection 
Protective Functions 
Other Function 
Protection for overheating of heat sink, over torque detection, 
error contact control, reverse prohibit, prohibit for direct start 
after power up and error recovery, parameter lock up.