v
Step 2 Apply Power to the Drive
z Apply AC power to the Drive and observe Operator. Five 7-segment Display
should read Power Voltage for 2 seconds and then read Frequency/Speed,
5.00. Five 7-segment Display and FWD LED should be flashed all the time.
Step 3 Check Motor Rotations without Load
z Press RUN key (FWD LED should light); five 7-segment Display should run
from 0.00 to 5.00.
z Check motor rotation.
If it is not correct:
Press STOP key. Remove AC power. Wait for LED “charge” lamp to extinguish.
Reverse motor leads T1 and T2.Restart the drive and check new rotation.
Step 4 Check Full Speeds at 50Hz/60Hz
z Frequency/Speed can be changed by pressing the up or down Arrow keys.
To move right or left for next digit, press “<” key.
Press the READ / ENTER key to set the speed.
z Set frequency up to 50Hz/60Hz in accordance with the last rule.
z Press RUN key. Check drives acceleration to full speed.
z Press STOP key to stop drive and check deceleration.
Step 5 Other Operations
Run command selection: 00-03(or 00-04)
Frequency command selection: 00-05(or 00-06)
For information, see N310 Instruction Manual.
Please refer to the following pages:
Set Control Mode (Vector, V/F) .............................…. p. 4-07
Set Motor Rated Current .......................................…. p. 4-13
Set Accel ......................................................................p. 4-08
Set Decel ..................................................................... p. 4-08
Set Max Speed ............................................................ p. 4-08
Set Min Speed ............................................................. p. 4-08