Chapter 4 Software Index
4-32
If set 01-13=0 0 0 0 0, means S1~S5 types of switches is Normal open, otherwise, if each bit of
01-13 is set to “1”, types of switches is Normal close.
Don’t set 00-03/00-04=1 , before you set 01-13, 01-14 (external terminal controlled)
Group2- External terminal analog signal input function group
02-00: AI1/AI2 analog Input signal type select
=0: AI1 0~10V(0~20mA), AI2 0~10V (0~20mA)
=1: AI1 0~10V(0~20mA), AI2 2~10V (4~20mA)
=2: AI1 2~10V(4~20mA), AI2 0~10V (0~20mA)
=3: AI1 2~10V(4~20mA), AI2 2~10V (4~20mA)
02-00: AI1/AI2 analog Input signal type select (refer to P3-14)
1. 0~10V(0~20mA)
2. 2~10V(4~20mA)
02-01: AI1 signal verification Scan Time 1–200 (×2mSec)
02-02: AI1 Gain(%) 0 - 1000
02-03: AI1 Bias(%) 0.0 – 100.0
02-04: AI1 Bias Selection 0:positive 1:Negative
02-05: AI1 Slope 0:positive 1:Negative
02-06: AI2 function Select
=0:PID feedback signal
=1:AI2 Bias signal input
1. 02-06=0 (PID feedback input)
When 02-06 is set 0 means the PID feedback input terminal is controlled by the setting of 09-00.
2. 02-06=1 (Bias Input)
To regulate the Offset of the Keypad VR or AI1 analog input, only the signal of 0~10V (0~20
mA) or 2~10V (4~20mA).
02-06=1function
V
10
0
Freq upper limit
00-07
Hz
AI1+AI2