Chapter 4 Software Index
4-45
the motor will run for 1 minute.
2. The heat sinking function will not be as effective when the motor run at low speed. So the
thermal relay action level will decline at the same time. (The curve 1 will change to curve 2).
3. 07-06 = 0: Set 06-04 as the rated frequency of the serve motor.
4. 07-08 = 0: the inverter coast to stop as the thermal relay acts and flash OL1. Press the
‘Reset’ or the external reset terminal to continue to run
= 1: the inverter continues to run as the thermal relay acts and flash OL1. Until the
current decline to 103% or 113 %( determined by 9-10), OL1 will disappear.
Minute
(1)
(2)
07-09: Over torque Detection Selection(OL3)
= 0: Disable Over torque Operation
= 1: Enable Over torque Operation Only if at Set Frequency
= 2: Enable Over torque Operation while the Drive is in Run Mode
07-10: Operation After Over torque Detection is Activated
= 0: Coast-to-Stop After Over torque is Activated
= 1: Drive will Continue to Operate After Over torque is Activated
07-11: Over torque Threshold Level(%): 30 ~ 300
07-12: Over torque Activation Delay Time (Seconds): 0.0 ~ 25.0
1. Over Torque is detected when the output torque level exceeds the level set in
Parameter 07-11 ( Inverter rated torque is 100%) and if it is detected for a duration of time
which is set in parameter 07-12.
2. 07-10 =0: If there is over torque, the inverter coasts to stop and flashes OL3. It is necessary to
press’RESET’ or external terminal to continue to run.
= 1: If there is over torque, the inverter can continue to run and flashes OL3 until the output
torque is less than the 07-11 set value.
3. Parameter 01-09/10(Multifunction output terminal) = 12, the output terminal signal will be set
for over torque condition.
Note: Over torque detection will be enabled only when parameter 07-09 is set to options 1or2.
07-13: OH over heat Protection ( cooling fan control)
0: 0: Auto (Depends on temp.)
1: Operate while in RUN mode
2: Always Run
3: Disabled
1. 07-13=0: The fan runs as the inverter senses temperature rises. Thusly, extend the service period.
2. 07-13=1: The fan runs while the inverter is running.
3. 07-13=2: The fan is continuously running regardless of the action of the inverter.
4. 07-13=3: The fan is Disabled.
Current Percent
150
1.0