EasyManuals Logo

TECO TP03 PLC User Manual

TECO TP03 PLC
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #64 background imageLoading...
Page #64 background image
Chapter 3 Expansion unit specification
expansion unit 3-4
1.3.2 TP02-16EYR Specification
Item Specification Outline figure
Input point 0
Output point 16
Voltage AC250V/DC30V
Current
2A/1
point ;5A/1common
Type Relay
Mechanical lifespan 20,000,000 times
Electric lifespan 150,000 times @ 3A
Response time Below 10ms
Min load 1 mA @ 5vDC
Indicator
LED LIT when output
ON
Output
Insulation Relay
Internal power supply:
Consumption current
For 5VDC: max 50mA
For 24VDC: max 80mA
Accessory
Expansion cable
(TP-042EC : 4cm
14pin)
Upside terminal block
8
1
3
6
COMC
24
5
7
COMD
7
COMA
6
3
1
2
5
4
8
COMB
Downside terminal block
Internal circuit
symbol content
1 ~ 8 Output terminal
Terminal
block
COM.A ~COM.D Common terminal
Note:
a. 4 points share one common terminal.
b. The common terminals with same symbol in upside
and downside are not connected internally.