Chapter 3 Expansion unit specification
expansion unit 3-15
2.1.3 Setting the system memory
Please set the system memory in advance, before try-run the connected units.
Setting
TP03 EXTEND MODULE
System memory
TP02
EXTEND
MODULE
ONLY
20/30 point
And S type
40/60 point
Def
ault
Remarks
D8256
Set the
number of Modules
(TP02-4AD+)
0~2 0 0~1 0
D8257
Set the
number of Modules
(TP03 input expansion units)
0 0~1 0~7 0
D8258
Set the
number of channels
(TP02-2DA+)
0~2 0 0~2 0
D8259
Set the
number of channels
(TP03 output expansion units)
0 0~2 0~8 0
20/30 and SR
type can’t
connect with
modules
mixed by
TP03 and
TP02 modules
D8260
AD software filter
(refer to next page for more)
0: no software filter
1~3: filter mode 1~3
0
D8261
AD Channel
1~4
D8262
AD Channel
5~8
… …
D8274
AD Channel
53~56
D8275
AD Channel
57~60
D8276
Operation mode for AD module: to set 4 HEX codes Hxxxx in Register
#D8261~D8276.
=0: AD mode is disabled;
=1: 0~10V voltage input mode(0~4000);
=2: 0~20mA current input mode(0~2000);
=3: 4~20mA current input mode or 1~5V voltage input mode(0~2000);
=4: PT100
=5: PT1000
=6:
=7:
=8: J-K
H00
00
Reserved AD
Channel
61~64
D8277
DA Channel
1~4
D8278
DA Channel
5~8
D8279
Operation mode for DA module: to set 4 HEX codes Hxxxx in Register
#D8277~D8279.
=0: DA mode is disabled;
=1: 0~10V voltage input mode(0~4000);
=2: 0~20mA current input mode(0~2000);
=3: 4~20mA current input mode /1~5V voltage input mode (0~2000)。
0
DA Channel
9~10
M825
7
number error for AD modules
1: D8256,D8257 set value exceeds the
range.
0
M825
8
Channel error for DA modules
1: D8258,D8259 set value exceeds the
range.
0
For example: AD mode D8261=H0123
AD CH1=3,4~20mA Current input mode or 1~5V Voltage input mode (0~2000);
AD CH2=2,0~20mA Current input mode (0~2000);
AD CH3=1,0~10V Voltage input mode (0~4000);