38
3 Initial Settings
You can select the initial setting procedure from the following three variations.
Regarding “3-3.Setting up by the controller only”, these settings cannot be done for models whose software version is earlier 
than 10.1.7.0.
Also, if you are setting up with just a controller, the following settings cannot be done.
•Linked control settings
•Master/slave settings for indoor units
•Floor and tenant settings
•Digital input/output interface and electric power meter interface settings
•Building name settings
•Power peak cut settings
3-1. Setup Using Template File of SFC2
Control functions that use power peak cut conditions cannot be set when using a template.
Set the control functions that use power peak cut conditions by the method that uses SFC2.
(1)Start up the Setting File Creation Software 2, select [Tools] - [Export Template] - [Touch Screen Controller] - [BMS-CT256U-
E/-TR], and then export a template file.
(2)Input the various items, "Building Name", "IP Address", "Air Conditioner Information", "Digital I/O Interface", and "Electric 
Power Meter Interface", in the template file.
(3)Start up the Setting File Creation Software 2. Select [Tools] - [Import] - [Touch Screen Controller] - [BMS-CT256U-E/-TR], 
and then import the data for the template file.
Uploading Setting Data
* If connecting to the LAN is difficult after the installation work, do "Uploading Setting Data" before "3-13.Installation work". If 
connecting to the LAN is easy after the installation work, then you could do "Uploading Setting Data" after "3-13.Installation 
work".
(1)Confirm whether the settings match the system at the site.
(2)Use a LAN cable to connect the Touch Screen Controller to the computer on which the Setting File Creation Software 2 is 
installed.
(3)Turn on the power to the controller, and confirm that the HOME screen is displayed (takes about 4 minutes).
(4)Put the computer’s IP address to 192.168.2.80, the same network as the Touch Screen Controller.
(5)Display the "Upload Settings" by using "File" - "Upload" in the Setting File Creation Software 2.
(6) Use the [ping] button to confirm the connection to the Touch Screen Controller.
(7) Use the "Upload" button to upload the setting file to the Touch Screen Controller.
When using the template function of the Setting File Creation Software 2