51
When you use a remote controller less unit to connect indoor units that are compatible with TU2C-LINK, you need to use one 
of the following methods to do remote controller less settings for the indoor unit. If these settings are not done, a Check Code 
E03 (Indoor - Remote controller communication error) is detected.
• On the wired remote controller or energy-saving neo remote controller, change DN [103] from 0 (with remote controller) → 
1 (remote controller less)
• On the System Controller being used, change DN [103] from 0 (with remote controller) → 1 (remote controller less) for the 
relevant indoor units*
*Limited to compatible Central Control Devices.
3-11.Comm software update
This screen is not used. Do not operate it.
When you connect the System Controller, set a central management address (DN03) for each indoor unit. Central management 
addresses require that you register separate numbers for each indoor unit, but if you mistakenly register the same central 
management address for different indoor units, an L20 (duplicated central control addresses) warning will be detected by 
System Controller or the local remote control.
With TU2C-LINK, the System Controller detects an L20. With TU2C-LINK, the remote controls belonging to the individual indoor 
units detect an L20. The System Controller, which is incompatible with TU2C-LINK, may not be able to detect an L20, depending 
on conditions*, if the indoor unit is compatible with TU2C-LINK. Be sure to do a one-to-one test for the System Controller and 
indoor units.
There are some models on which you can check for duplications on the central management address list screen, depending on 
the model of the System Controller.
* Central Control Devices whose model name does not contain "U"
[Conditions]
When the same central management address is set for indoor units using different coolant systems in a system of outdoor units 
and indoor units that are compatible with TU2C-LINK and a Central Control Device that is incompatible with TU2C-LINK.
Settings to Connect a Machine That Has No Remote Control
About L20 (Duplicated central control addresses) Warnings
Remote controller 
less devices
System Controller