48
3-9. Old controller setting
This setting screen is for combining Central Control Devices that are not compatible with TU2C-LINK.
* This screen can only be set if "Old controller setting" is selected in the "Comm settings" screen.
Select models to use in combination.
When using in combination with Smart BMS manager or web compatible central remote controller
• Smart BMS manager/web compatible central remote controller: Setting not needed
• Main unit: Set as slave unit
When "used with BMS-CT512*" is set in the combination settings, this setting cannot be changed.
The address used when doing TU2C-LINK communications is changed.
Do not change this setting from the initial value (ALL group).
When "Used with BMS-CT512*" is set in the combination settings, this setting cannot be changed.
Do not change this setting from the initial value (OFF).
1 Tap [1-(1)].
1 Combination setting
2 Parent-child setting
3 Managed unit mode setting
4 Central address ragular communication
1
-(1)
Item Description
Used with other than BMS- CT512*
Set when used with models other than BMS-CT512*.
(The address used when doing TU2C-LINK communications is 0x300)
Used with BMS-CT512*
Set when used with BMS-CT512*.
(The address used when doing TU2C-LINK communications is other than
0x300)
Item
Description
Parent
Set this when the main unit is used independently or is used as a master unit connected to other Central
Control Devices.
(Put only one master unit on TU2C-LINK.)
Child
Set this when there are 2 or more main units or other Central Control Devices are being used in combination
and one is being used as a slave unit.
(Put only one master unit on TU2C-LINK.)