23.24 ATS Category Timings
This table describes the EN50136-1 ATS Category Timings laid down in the standard and how the
FlexC implementation meets these standards under the categories SP1-SP6, DP1-DP4.
EN50136-1 ATS Category Timing
Requirements
FlexC Implementation of ATS Category
Timing Requirements
ATS
Category
Default
Interfaces
Event
Timeout
Primary
Polling
Timeout
Backup ATP
Polling
Timeout
(Primary OK)
Backup ATP
Polling
Timeout
(Primary
Down)
Event
Timeout
Primary
Polling
Timeout
Backup
ATP Polling
Timeout
(Primary
OK)
Backup ATP
Polling
Timeout
(Primary
Down)
SP1 Cat 1
[Ethernet]
8 min 32 days - - 2 min 30 days - -
SP2 Cat 2
[Ethernet]
2 min 25 hr - - 2 min 24 hr - -
SP3 Cat 3
[Ethernet]
60 s 30 min - - 60 s 30 min - -
SP4 Cat 4
[Ethernet]
60 s 3 min - - 60 s 3 min - -
SP5 Cat 5
[Ethernet]
30 s 90 s - - 30 s 90 s - -
SP6 Cat 6
[Ethernet]
30 s 20 s - - 30 s 20 s - -
DP1 Cat 2
[Ethernet]
Cat 2
[Modem]
2 min 25 hr 50 hr 25 hr 2 min 24 hr 24 hr 30 min 24 hr 10 min
DP2 Cat 3
[Ethernet]
Cat 3
[Modem]
60 s 30 min 25 hr 30 min 60 s 30 min 24 hr 30 min 30 min
DP3 Cat 4
[Ethernet]
Cat 4
[Modem]
60 s 3 min 25 hr 3 min 60 s 3 min 24 hr 30 min 3 min
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Appendix
© Vanderbilt 2018 397 A6V10276959-d