l Add Dual Path Dual Server ATS
l Add Custom ATS
3. For an EN50136 ATS, you must configure the settings on the ATP Configuration - EN50136
page first. See Quick Start ATP Configuration for EN50136 ATS on page305.
4. The ATS Configuration page displays. An EN50136-1 ATS will display a primary or primary
and backup ATP in the Event Sequence Table.
5. Enter an ATS Name to identify the ATS. If you do not enter a value, the ATS name defaults to
ATS 1, ATS 2, etc.
6. To add 1 primary and up to 9 backup ATPs to an ATS, click Add ATP to FlexC RCT (see Add
ATP to FlexC RCT on the next page) or click Add ATP to Analog ARC (see Add ATP to
Analog ARC on page314).
7. Select an Event Profile from the dropdown menu. To customise how events are transmitted on
an ATS, see Configuring Event Profiles on page319.
8. Select a Command Profile from the dropdown menu. To customise the commands enabled for
an RCT to control a panel, see Configuring Command Profiles on page322.
9. Complete the ATS Faults fields as shown in the table below.
ATS
Polling
Timeout
This field is automatically calculated by adding the values of the Active Polling
Timeout column in the Event Sequence Table, that is, for all ATPs in an ATS.
You can manually overwrite this field. For example, CAT 2 [Modem] has an
Active Polling Timeout of 24 hours 10 minutes (87000 seconds). To allow a
shorter reaction time, enter a lower value.
ATS
Event
Timeout
The amount of time after an event has been raised and not successfully
transmitted before the ATS gives up. Default: 300 seconds.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2018 308 A6V10276959-d
11.2018