ID Zone ID Zone ID Zones ID Zones ID Zones
2 17-24 15 121-128 28 225-232 41 329-336 54 433-440
3 25-32 16 129-136 29 233-240 42 337-344 55 441-448
4 33-40 17 137-144 30 241-248 43 345-352 56 449-456
5 41-48 18 145-152 31 249-256 44 353-360 57 457-464
6 49-56 19 153-160 32 257-264 45 361-368 58 465-472
7 57-64 20 161-168 33 265-272 46 369-376 59 473-480
8 65-72 21 169-176 34 273-280 47 377-384 60 481-488
9 73-80 22 177-184 35 281-288 48 385-392 61 489-496
10 81-88 23 185-192 36 289-296 49 393-400 62 497-504
11 89-96 24 193-200 37 297-304 50 401-408 63 505-512
12 97-104 25 201-208 38 305-312 51 409-416
13 105-112 26 209-216 39 313-320 52 417-424
If 2 devices of a kind (for example, expanders) are set to same ID, upon configuration, both
expanders beep and the flashing LED indicates conflict. Reset the switches and the system
rescans.
On a device, if both rotary switches are set to zero (0, 0), the full configuration becomes an
automatic addressing configuration.
To select the ADDRESS MODE:
1. Scroll to ADDRESS MODE.
2. Press SELECT.
3. Toggle for appropriate address mode: AUTOMATIC or MANUAL
4. Press SELECT to update the setting.
16.6.6 XBUS Type
To program the X-BUS type from the keypad:
1. Scroll to XBUS TYPE.
2. Press SELECT.
3. Scroll to select desired configuration:
- LOOP
- SPUR
4. Press SELECT to update the setting.
16.6.7 Bus Retries
To program the number of times the system attempts to retransmit data on the X-BUS interface before
a communications fault is generated:
1. Scroll to BUS RETRIES.
2. Press SELECT.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Engineer programming via the keypad
© Vanderbilt 2018 134 A6V10276959-d
11.2018