VdS 2471
Compatible
(Vds standard only)
If this option is selected then the EDP receiver will enforce the
following settings for that receiver:
l 8s polling interval
l TCP protocol enforced
l TCP retries will fail before 10s (9s approx)
l EDP event retries are set to 1 independent of the global “Retry
Count” setting in “EDP Settings”
l FTC will be generated within 20s of network failure.
Security
Commands Enable Check this box to allow commands to be accepted from the receiver.
Change User PINs Check this box to allow user PINs to be changed from a remote
location. This feature is applicable only if commands are enabled from
the receiver.
Encryption Enable Check this box to enable encryption on data to and from the receiver.
Encryption Key Enter a hexadecimal key (max. 32 digits) that will be used to encrypt
the data.
Note: The same key will need to be used at the receiver.
Virtual Keypad Enables access to the panel with a virtual keypad, that is, a PC
software module that looks and behaves like an SPC keypad. It is
available with the SPC Com client.
Live
Streaming/Streaming
Mode
Specifies when live streaming of audio and video is available. Options
are Never, Always or Only after an alarm event. Default is ‘Only after
an alarm event’.
Note: This setting has obvious privacy implications and therefore
should be enabled only where appropriate and subject to local laws and
regulations.
Network (Applies to the Ethernet connection only)
Network Enable Check this box to allow events to be reported through the network.
Network Protocol Select the type of network protocol for the receiver. Options are UDP
and TCP. TCP is recommended if supported by the receiver.
Receiver ID Address Enter the IP address of the receiver.
Receiver IP Port Enter the IP port that the EDP receiver is listening on.
Always Connected If enabled the panel will keep a permanent connection to the receiver. If
disabled, the panel will only connect to the receiver after an alarm
event.
Panel Master If enabled the panel is master of polling messages. Only applicable to
UDP connections.
Polling Interval Enter the number of seconds between polls.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Engineer programming via the browser