Interlock
Group
Select an Interlock Group to assign to this area. Interlocking only allows one area within the group to
be Unset at any time. Typically used in ATM areas.
Unset
Duration
If area is Unset for longer than this it will Set automatically. (Range 0–120 mins: 0=notactive).
Dual PIN If this option is enabled, two PINs are required to Set or Unset the area with the keypad. Both PINs
must belong to users who have the required user right for the operation (Setting or Unsetting).
If the second PIN is not entered within 30 seconds, or it is wrong, then the area cannot be Set or
Unset.
Force Set
Mode
Area options for Force-set operation (Normal or Blocked).
Auto
Restore
on Force
Set
Check this option to auto-restore closed zones during force-set. If this option is selected, if an alert is
active or a zone needs to be restored, then it will be automatically restored.
Late Working Support
An example of using the setting and unsetting parameters is for late working situations where a
calendar has been configured for automatic setting of a premises at a particular time but staff may need
to work late on occasion and the automatic setting needs to be delayed.
Each delay is determined by the amount configured in the Delay Interval parameter, and the Delay
Counter parameter determines the number of times that setting can be delayed. A user needs the
correct value in the Auto Set Delay in order to use this feature.
There are three ways to delay setting:
1. Entering the PIN on the keypad.
DELAY is a menu option on the standard keypad. The buttons at the top of the comfort keypad
are used to operate the delay feature
2. Using the keyswitch.
Turning the key to the right delays setting the system by the configured delay if the maximum
number of times that setting can be delayed (Delay Counter) has not been exceeded. Turning
the key to the left sets the delay to three minutes (non-configurable). This can be done regardless
of how many times setting was delayed.
3. Using a FOB, WPA or button which activates a Delay Autoset trigger action.
Temporary Unset
To allow a system to be temporarily unset in a time period specified by a calendar, the following three
parameters need to be configured:
1. Calendar
A calendar needs to be configured and selected for this area.
2. Time Locked
This box needs to be ticked so that the area can be unset only when allowed as per the
configured calendar.
3. Unset Duration
This parameter needs to be set to a value greater than zero to set an upper limit on the time the
area will be unset.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2018 276 A6V10276959-d
11.2018

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vanderbilt SPC42 Series and is the answer not in the manual?

Vanderbilt SPC42 Series Specifications

General IconGeneral
BrandVanderbilt
ModelSPC42 Series
CategoryPower Supply
LanguageEnglish

Related product manuals