EasyManua.ls Logo

Vertiv NetSure M830B - Table of TL1 Commands Supported

Vertiv NetSure M830B
274 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv™ NetSure™ Control Unit (NCU) User Manual
242
TL1 Autonomous Message Sample
The DI1 alarm occurs.
When the alarm occurs, the controller sends this autonomous message:
LorainLab 15-09-24 13:49:42
*C 8 REPT ALM EQPT
"PowerSystem:CR,Alarm,SA,09-24,13-49-41,,,0,0,0-MIN:\"DI1 Alarm\","
;
<
When the alarm clears, the controller sends this autonomous message:
LorainLab 15-09-24 13:50:06
A 9 REPT ALM EQPT
"PowerSystem:CL,Alarm,SA,09-24,13-50-06,,,0,1,0-MIN:\"DI1 Alarm\","
;
<
7.4.3 Table of TL1 Commands Supported
Refer to Table 7.1 for a list of all TL1 commands supported, with a short description of each command.
Table 7.1 TL1 Commands Supported
TL1 Commands Supported Description
ACTIVATE-USER
ACT-USER
Sets up a session with the system (i.e., logging into the system).
CANCEL-USER
CANC-USER
Terminates a session with the system (i.e., logging off of the system).
RETRIEVE-ALARM
RTRV-ALM-{EQPT|ALL}
Instructs the system to send the current state of its alarm conditions associated with one or
more equipment units, facilities, etc. within the system.
RETRIEVE-EQUIPMENT
RTRV-EQPT
Instructs the system to send the current controller software version and the controller
software configuration part number and revision.
RETRIEVE-HEADER
RTRV-HDR
Requests that the system reply with a "normal" response indicating COMPLD.