Vertiv™ NetSure™ Control Unit (NCU) User Manual
• Equalize Start Capacity
• Equalize Stop Current
• Equalize Stop Delay Time
• Maximum Equalize Charge Time
2.9.19 Programming the Audible Alarm Feature
Local Menu Navigation:
Main Menu / Settings Icon / Alarm Settings / Audible Alarm.
Web Menu Navigation:
Settings Menu / System Tab / LCD Audible Alarm.
2.9.20 Manually Forcing LVDs
Local Menu Navigation:
Main Menu / Settings Icon / Maintenance / “Auto/Man” State (change to Manual).
then
Main Menu / Settings Icon / Maintenance / LVD 1 Control or LVD 2 Control (select the other state).
then
Main Menu / Settings Icon / Maintenance / LVD 1 Control or LVD 2 Control (select the original state).
then
Main Menu / Settings Icon / Maintenance / “Auto/Man” State (change to Auto).
Web Menu Navigation:
Settings Menu / System Tab / “Auto/Manual” State (change to Manual).
then
Settings Menu / LVD Tab / LVD 1 Control or LVD 2 Control (select the other state).
then
Settings Menu / LVD Tab / LVD 1 Control or LVD 2 Control (select the original state).
then
Settings Menu / System Tab / “Auto/Manual” State (change to Auto).
2.9.21 Manually Forcing Relays
After completing the following steps, the relay will momentarily toggle to the chosen state. The relay then reverts back to being
controlled by the NCU.
NOTE!
This may take a few minutes.
See also “Using the Relay Test Feature” on page 46.
Local Menu Navigation:
None.
Web Menu Navigation:
Settings Menu / System Tab / “Auto/Manual” State (change to Manual).
then
Advance Settings Menu / DO (relay) / Relay (select the other state) then press the SET button.
then
Settings Menu / System Tab / Power System / “Auto/Manual” State (change to Auto).