EasyManua.ls Logo

Vertiv NetSure M830B - Setting the SM-DUE Parameters (if Furnished)

Vertiv NetSure M830B
274 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv™ NetSure™ Control Unit (NCU) User Manual
44
Break Value (Device Rating)
High 1 Curr Limit Alarm (% of Breaker Value)
High 1 Curr Alarm Severity
High 1 Curr Alarm Relay
High 2 Curr Limit Alarm (% of Breaker Value)
High 2 Curr Alarm Severity
High 2 Curr Alarm Relay
WEB Menu Navigation (for shunts set as battery):
Settings Menu / Quick Settings Tab / Signal Settings Section / SMDU#Batt# Rated Capacity and enter the following parameters.
Parameters
SMDU#Batt#, Rated Capacity
2.9.49 Setting the SM-DUE Parameters (if furnished)
The SM-DUE is used to input external monitoring information to the NCU controller. The SM-DUE provides the following monitoring
inputs:
Ten (10) input blocks with each providing the following monitoring inputs:
- One (1) Load Bus Voltage (0 VDC to 60 VDC) per input block
- One (1) Load Fuse Alarm (Bus- base of 0 VDC, >10 VDC alarm, <10 VDC normal) per input block
- One (1) Programmable Analog Input, can be set to accept one (1) of the following inputs per input block:
10 mV DC to 50 mV DC Load Shunt
General-Purpose Current Transducer
General-Purpose Voltage Transducer
1 uA/K Temperature Sensor
Program these inputs per site requirements as detailed next.
Programming the SM-DUE Load Bus Voltage Input
Local Menu Navigation:
None.
Web Menu Navigation:
Advance Settings Menu / Custom Inputs Tab / SMDUE # / Input Block #,
press “Modify” and select “Enable” for the voltage input. When done, press “Set”.
Close the window by clicking on the X button.
Go to the Advanced Settings Menu > Analogs Tab and set the voltage input parameters.
Programming the SM-DUE Load Fuse Alarm Input
Local Menu Navigation:
None.

Table of Contents

Related product manuals