Vertiv™ NetSure™ Control Unit (NCU) User Manual
48
3. Start the battery discharge test.
Local Menu: Main Menu / Settings Icon / Maintenance / BattTestControl.
Web Menu: Settings Menu / Battery Test / Battery Test Control.
4. Wait for the test to end.
5. View the battery test log and upload it to your computer as required. See “Battery Test Log Tab” on page 162.
2.9.55 Updating the NCU Controller’s Device Inventory
Local Menu Navigation:
Main Menu / Settings Icon / Other Settings / Auto Config.
Web Menu Navigation:
Advance Settings Menu / SW Maintenance Tab / Auto Config.
2.9.56 Backing Up the NCU Configuration
To back up the NCU configuration, simply save the file named "SettingParam.tar".
NOTE!
It is strongly recommended that you save a copy of the “SettingParam.tar file whenever you make any changes to
the NCU. Then, if you ever replace the NCU or perform a "Restore Defaults" procedure, you can restore your customized
settings by downloading the previously saved “SettingParam.tar” file back into the NCU.
Prior to changing NCU settings, ensure the current "SettingParam.tar" file is backed up. After making changes, create a new backup
file.
To aid in file management, you may change the name of the "SettingParam.tar" file to differentiate it from other "SettingParam.tar" files
saved. The new name can use alpha and numeric characters preceding the original "SettingParam.tar" name (the end of the new file
name must always be "SettingParam.tar"; for example, an acceptable filename would be "seville4SettingParam.tar").
Saving the “SettingParam.tar” File
Local Menu Navigation:
None.
Web Menu Navigation:
Advance Settings Menu / SW Maintenance Tab.
See “Retrieve "SettingParam.tar" File Procedure” on page 189 to retrieve the “SettingParam.tar” file.
2.9.57 Reloading a Backed-Up NCU Configuration
To reload the NCU configuration, simply download a saved "SettingParam.tar" file into the NCU.
Reloading the “SettingParam.tar” File
Local Menu Navigation:
None.
Web Menu Navigation:
Advance Settings Menu / SW Maintenance Tab.
See “Upload/Download Procedure” on page 191 to download a "SettingParam.tar" file into the NCU.