Vertiv™ NetSure™ Control Unit (NCU) User Manual
261
Safety and Standards Compliance:
Electrical: IEC 60950-1, EN 60950-1, UL 60950-1
EMC: EN 300 386, 2001 Class B; FCC Part 15, Class B
Environmental: CE; NEBS Level 3
GR-3108 Class 2 Compliant
System Voltage Monitoring (Float / Equalize) Accuracy: 0.1 VDC, over the range of 0 VDC to +30 VDC and 0 VDC to -60 VDC
and from +15 °C to +30 °C.
Temperature Probe Accuracy:
Calibration Error (-25 °C to +105 °C): ±2 °C
Nonlinearity (-25 °C to +105 °C): 0.4 °C
NCU Temperature Probe Input Accuracy (-10 °C to +65 °C): ±2 °C