Manual VIPA CPU 21x Chapter 9 Deployment CPU 21xSER-1
HB103E - Rev. 05/45 9-13
Value Description
0000h no error
809Ah interface not found
8x24h Error at SFC-Parameter x, with x:
1: Error at "Protocol"
2: Error at "Parameter"
3: Error at "Baudrate"
4: Error at "CharLength"
5: Error at "Parity"
6: Error at "StopBits"
7: Error at "FlowControl"
809xh Error in SFC parameter value x, where x:
1: Error at "Protocol"
3: Error at "Baudrate"
4: Error at "CharLength"
5: Error at "Parity"
6: Error at "StopBits"
7: Error at "FlowControl"
8092h Access error in parameter DB (DB too short)
828xh Error in parameter x of DB parameter, where x:
1: Error 1
st
parameter
2: Error 2
nd
parameter
...
RetVal
(Return value)